7. <Check Removal Completion>
(1) Click [Close] in the “Remove Disk Board” window.
If a message other than the following is displayed, refer to Message Section (MSG00-00).
(2) <Check back up the encryption key Messages>
When the encryption environment is applied, the following message is displayed.
Check the message and click [Close].
(3) Checking Normality
Perform the procedure described in "Checking Normality" (TRBL02-06-10).
(4) Click [Logout] to close the window.
8. Removing the Maintenance PC
Remove the Maintenance PC from the storage system referring to “Attachment/Removal Procedure of
Maintenance PC” (INST(IN)13-02-10).
9. Back up the encryption key
If the message is displayed in Step 7(2), ask your customer to back up the encryption key using Storage
Navigator (refer to Encryption License Key User Guide).
NOTE: When a message is not displayed in Step 7(2), this procedure is not required.