EasyManuals Logo

Hitachi L100 Series Quick Reference Guide

Hitachi L100 Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
10
Error Trip Conditions
Use function code D_08 to access the error trip conditions for the
current error as shown in the table below. Use the Up and Down
arrow keys to scroll through the trip condition parameters.
E35
Thermistor Thermistor input, [THM] and [L], is
over the temp. threshold
---
Under-voltage (brown-
out) with output shutoff
Low input voltage caused the
inverter to turn OFF the motor output
and try to restart. If unsuccessful, a
trip occurs.
Step Display
1. Access D_08
d 08
2. Press Function Key If no error:
_ _ _
If error exists:
Exx
(error code)
3. Press Up/Dn key (if
error exists)
Output frequency at
trip point:
10.0
Motor current at trip
point:
0.025
DC bus voltage at trip
point:
189.8
Error
Code
Name Probable Cause(s)
1
2

Other manuals for Hitachi L100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi L100 Series and is the answer not in the manual?

Hitachi L100 Series Specifications

General IconGeneral
BrandHitachi
ModelL100 Series
CategoryInverter
LanguageEnglish

Related product manuals