17
“B” Group: Fine-tuning Functions
A_82 AVR voltage select 230/230/200
400/460/400
A_92 Acceleration (2) time setting 15.0
A_93 Deceleration (2) time setting 15.0
A_94 Select method to switch to Acc2/Dec2
profile
00 2CH input from terminal
01 transition frequency
00
A_95 Acc1 to Acc2 frequency transition point 0.0
A_96 Dec1 to Dec2 frequency transition point 0.0
A_97 Acceleration curve selection
00 Linear 01 S-curve
00
A_98 Deceleration curve selection
00 Linear 01 S-curve
00
Func.
Code
Name / Description
Default
Value
–FE / –FU /
–FR
Set
Value
B_01 Selection of automatic restart mode
00 Alarm output after trip, automatic
restart disabled
01 Restart at 0Hz
02 Resume operation after frequency
matching
03 Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info
00
B_02 Allowable under-voltage power failure
time
1.0
B_03 Retry wait time before motor restart 1.0
Func.
Code
Name / Description
Default
Value
–FE / –FU /
–FR
Set
Value

Other manuals for Hitachi L100 Series