24
B022 Overload restriction setting Rated
current x
1.20 / 1.10 /
1.20
B023 Deceleration rate at overload restriction 1.00 / 15.00
/ 1.00
B024 Overload restriction operation mode (2)
00 Disabled
01 Enabled for accel and constant speed
02 Enabled for constant speed only
01
B025 Overload restriction setting (2) Rated
current
x 1.20
B026 Deceleration rate at overload restriction (2) 1.00
B031 Software lock mode selection
00 Low-level access, [SFT] blocks edits
01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
02 No access to edits
03 No access to edits except F001 and Multi-
speed parameters
10 High-level access, including B031
01
B034 Run/power on warning time 0.
B035 Rotational direction restriction
00 Enable for both directions
01 Enable for forward only
02 Enable for reverse only
00
B036 Reduced voltage start selection
00 Short
01, 02, 03, 04, 05 (middle)
06 Long
06
B037 Function code display restriction
00 Display all
01 Display only utilized functions
02 Display user-selected functions only
(configure with U01 to U12)
00
B080 [AM] terminal analog meter adjustment 180
B081 [FM] terminal analog meter adjustment 60
B082 Start frequency adjustment 0.50
B083 Carrier frequency setting 3.0
Func.
Code
Name / Description
Default
Valu e
–FE2/–FU2/
–FR
Set
Valu e

Other manuals for Hitachi L300P Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi L300P Series and is the answer not in the manual?

Hitachi L300P Series Specifications

General IconGeneral
BrandHitachi
ModelL300P Series
CategoryInverter
LanguageEnglish

Related product manuals