24
B022 Overload restriction setting Rated
current x
1.20 / 1.10 /
1.20
B023 Deceleration rate at overload restriction 1.00 / 15.00
/ 1.00
B024 Overload restriction operation mode (2)
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
01
B025 Overload restriction setting (2) Rated
current
x 1.20
B026 Deceleration rate at overload restriction (2) 1.00
B031 Software lock mode selection
• 00 Low-level access, [SFT] blocks edits
• 01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
• 02 No access to edits
• 03 No access to edits except F001 and Multi-
speed parameters
• 10 High-level access, including B031
01
B034 Run/power on warning time 0.
B035 Rotational direction restriction
• 00 Enable for both directions
• 01 Enable for forward only
• 02 Enable for reverse only
00
B036 Reduced voltage start selection
• 00 Short
• 01, 02, 03, 04, 05 (middle)
• 06 Long
06
B037 Function code display restriction
• 00 Display all
• 01 Display only utilized functions
• 02 Display user-selected functions only
(configure with U01 to U12)
00
B080 [AM] terminal analog meter adjustment 180
B081 [FM] terminal analog meter adjustment 60
B082 Start frequency adjustment 0.50
B083 Carrier frequency setting 3.0
Func.
Code
Name / Description
Default
Valu e
–FE2/–FU2/
–FR
Set
Valu e