EasyManua.ls Logo

Hitachi L300P Series - Page 15

Hitachi L300P Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1- 12
Function Mode
Code Function name L300P Setting range
Initial data
-FE/-FU/-FR
N o t e
A061 1
st
frequency upper limiter 0.00, 1
st
frequency lower limiter-maximum frequency(Hz) 0.00
A261 2
nd
frequency upper limiter 0.00, 2
nd
frequency lower limiter-2
nd
setting maximum
frequency(Hz)
0.00
A062 1
st
frequency lower limiter 0.00, start frequency-maximum frequency(Hz) 0.00
A262 2
nd
frequency lower limiter 0.00, start frequency-2
nd
setting maximum frequency(Hz) 0.00
A063 Jump frequency1 0.00-99.99/100.0-400.0(Hz) 0.00
A064 Jump frequency Width 1 0.00-10.00(Hz) 0.50
A065 Jump frequency2 0.00-99.99/100.0-400.0(Hz) 0.00
A066 Jump frequency Width 2 0.00-10.00(Hz) 0.50
A067 Jump frequency3 0.00-99.99/100.0-400.0(Hz) 0.00
A068 Jump frequency Width 3 0.00-10.00(Hz) 0.50
A069 Acceleration stop frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A070 Acceleration stop time 0.00-60.0(s) 0.0
A071 PID selection 00(invalid)/01(valid) 00
A072 PID-P gain 0.2-5.0 1.0
A073 PID-I gain 0.0-3600.(s) 1.0
A074 PID-D gain 0.00-100.0(s) 0.00
A075 PID scale 0.01-99.99 1.00
A076 PID feedback selection 00(feedback : OI)/01(feedback : O) 00
A081 AVR selection 00(ON always)/01(OFF always)/02(OFF on decelerating) 00/00/02
A082 Motor voltage selection 200/215/220/230/240, 380/400/415/440/460/480
(230/400)
(230/460)
(200/400)
A085 Operation mode selection 00(normal operation)/01(energy-saving operation) 00
A086
Energy-saving response-
accuracy adjustment
0.0-100.0 50.0
A092 Acceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A292 2
nd
acceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A093 Deceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A293 2
nd
deceleration time2 0.01-99.99/100.0-999.9/1000.-3600.(s) 15.00
A094 2
nd
stage adjustable selection 00(change with 2CH terminal)/01(change with setting) 00
A294
2
nd
stage adjustable
selection(2
nd
motor)
00(change with 2CH terminal)/01(change with setting) 00
A095 2
nd
acceleration frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A295
2
nd
acceleration
frequency(2
nd
motor)
0.00-99.99/100.0-400.0(Hz) 0.00
A096 2
nd
deceleration frequency 0.00-99.99/100.0-400.0(Hz) 0.00
A296
2
nd
deceleration frequency
(2
nd
motor)
0.00-99.99/100.0-400.0(Hz) 0.00
A097 Acceleration pattern selection 00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve) 00
A098 Deceleration pattern selection 00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve) 00
A101 OI start 0.00-99.99/100.0-400.0(Hz) 0.00
A102 OI end 0.00-99.99/100.0-400.0(Hz) 0.00
A103 OI start rate 0.-100. ( %) 20.
A104 OI end rate 0.-100. ( %) 100.
A105 OI start selection 00(external start frequency)/01(0Hz) 01
A111 O2 start -400.--100./-99.9-0.00-99.9/100.-400.(Hz) 0.00
A112 O2 end -400.--100./-99.9-0.00-99.9/100.-400.(Hz) 0.00
A113 O2 start rate -100. - 100. (%) -100.
A114 O2 end rate -100. - 100. (%) 100.
A131 Acceleration curve constant 01(small swelling)-10(large swelling) 02
A132 Deceleration curve constant 01(small swelling-10(large swelling) 02
b001 Retry selection
00(trip)/01(0Hz start)/02(start after equal frequency)/
03(trip after equaling frequency and deceleration stop)
00
b002
Allowable under-voltage
power failure time
0.3-1.0(s) 1.0
b003 Retry wait time 0.3-100.(s) 1.0
b004
Instantaneous power-
failure/under-voltage trip
during stop
00(invalid/01(valid)/
02(invalid during stop and deceleration by stop command)
00
b005
Instantaneous power-
failure/under-voltage
retry time selection
00(16 times)/01(free) 00
b006 Open-phase selection 00(invalid)/01(valid) 00
b007 Frequency setting to match 0.00-99.99/100.0-400.0(Hz) 0.00
b012 Electronic thermal level 0.2*constant current-1.20*constant current(A)
Rated
Current of
inverter
b212
Electronic thermal level
(2
nd
motor)
0.2*constant current-1.20*constant current(A)
Rated
Current of
inverter
b013
Electronic thermal
characteristic selection
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
01/01/00
b213
Electronic thermal
characteristic selection
(2
nd
motor)
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
01/01/00
b015
Free electronic thermal
frequency 1
0.-400.(Hz) 0.
b016
Free electronic thermal
current 1
0.0-1000.(A) 0.0
b017
Free electronic thermal
frequency 2
0.-400.(Hz) 0.
b018
Free electronic thermal
current 2
0.0-1000. (A) 0.0
b019
Free electronic thermal
frequency 3
0.-400.(Hz) 0.
b020
Free electronic thermal
current 3
0.0-1000.(A) 0.0
limiter / jump
PID control
External frequency
adjustment
Operation mode/ adjustable function
Accel
Decel
Instantaneous power failure
restart

Other manuals for Hitachi L300P Series