L300P Supplement Explanation of functions
Function mode
Code Function name Setting range
LBRM/HFBM
Initial Data
LFU/HFU
Initial data
b034 RUN time/Power ON time level 0.-9999./1000-6553(10000-65530)hr 0. 0.
b035 Operation direction restrict 00(Reverse is valid)/01(Only forward)/02(Only reverse) 00 00
b036 Start reduced voltage
00(Start reduced voltage time small)-06(Start reduced voltage time
large)
06 06
b037 Display selection
00(all display)/01(each function display)/02(User setting,main
setting)
00 00
b080 AM adjustment 0. - 255. 180 180
b081 FM adjustment 0. - 255. 60 60
b082 Start frequency adjustment 0.10-9.99(Hz) 0.50 0.50
b083 Carrier frequency setting 0.5-12.0(kHz) Derating enable, 3.0 3.0
b084 Initialize mode
00(Trip history clear)/01(Data initialization)/
02(Trip history clear + data initialization)
00 00
b085 Country code for initialization 00(Interior)/01(EC)/02(USA) 02 02
b086
Frequency scalar conversion
factor
0.1-99.9 1.0 1.0
b087 STOP key enable 00(valid)/01(invalid) 00 00
b088
Resume on FRS cancellation
mode
00(0Hz start)/01(Start f-equaling) 00 00
b090 BRD usage ratio 0.0-100.0(%) 0.0 0.0
b091 Stop mode selection 00(deceleration stop)/01(Free-run stop) 01 00
b092 Cooling fan control
00(Always ON)/01(ON during run
〈After power ON, then for 5 minutes on stop is implied.〉)
00 00
b095 BRD selection
00(invalid)/01(valid〈invalid during stop〉)/02(valid〈valid during stop〉)
00 00
b096 BRD ON level 330-380/660-760(V) 360/720 360/720
b098 Thermistor selection
00(invalid)/01(Positive temperature coefficient enable)/
02 (NTC enable)
00 00
b099 Thermistor error level 0. – 9999. (ohm) 3000. 3000.
C091 Debug mode selection 00(No display)/01(Display) 00 00
C101 UP/DWN selection 00(No frequency data)/01(Keep frequency data) 00 00
C102 Reset selection
00(Trip cancel during ON)/01(Trip cancel during OFF)/
02(Valid only during trip〈Cancel during ON〉)
00 00
C103
Reset f frequency matching
selection
00(0Hz start)/01(Start f-equaling) 01 00
C121 O zero adjustment 0.-9999./1000-6553(10000-65530)
Set on
forwarding
Set on
forwarding
C122 OI zero adjustment 0.-9999./1000-6553(10000-65530)
Set on
forwarding
Set on
forwarding
The others
C123 O2 zero adjustment 0.-9999./1000-6553(10000-65530)
Set on
forwarding
Set on
forwarding
H003 1
st
motor capacity selection 0.20-75.0(kW)
Set on
forwarding
Set on
forwarding
H203 2
nd
motor capacity selection 0.20-75.0(kW)
Set on
forwarding
Set on
forwarding
H004 1
st
motor pole selection 2/4/6/8(pole) 4 4
H204 2
nd
motor pole selection 2/4/6/8(pole) 4 4
H006 1
st
stabilized factor 0. - 255. 100. 100.
H206 2
nd
stabilized factor 0. - 255. 100. 100.
P001
Option1 operation selection
on error
00(TRP)/01(RUN) 00 00
P002
Option2 operation selection
on error
00(TRP)/01(RUN) 00 00
P031
Input mode selection for
Digital input option
00(Mode 0)/01(Mode 1)/02(Mode 2) 00 00
P050
Frequency during the
loss of O,O2,OI input
00(invalid)/01(0Hz)/02(maximum Frequency )/03(multi speed 0)
NOTE (1)
00 00
U001 User1 selection no/d001-P050 no no
U002 User2 selection no/d001-P050 no no
U003 User3 selection no/d001-P050 no no
U004 User4 selection no/d001-P050 no no
U005 User5 selection no/d001-P050 no no
U006 User6 selection no/d001-P050 no no
U007 User7 selection no/d001-P050 no no
U008 User8 selection no/d001-P050 no no
U009 User9 selection no/d001-P050 no no
U010 User10 selection no/d001-P050 no no
U011 User11 selection no/d001-P050 no no
U012 User12 selection no/d001-P050 no no
NOTE (4) : See Page 2 (When O, OI, or O2 frequency reference input signal is lost)
11