EasyManuals Logo
Home>Hitachi>Air Compressor>NEXT Series

Hitachi NEXT Series User Manual

Hitachi NEXT Series
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
31
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
3.4.8 ECOMODE Function (only for Fixed speed type)
RUNNINGCONTROL
ALARM
1
REMOTE
STR
FUNC
RESET
SELECT/WIDE
1
SELECT/WIDE
SELECT/WIDE
Press the button for 7 seconds
or more to set.
ON : The light blinks.
OFF : The light turns off.
(1) Setting of ECOMODE (Energy Saving Mode)
ECOMODE is set OFF on factory setting. See
SELECT/WIDE button in
3.1 to be activated.
This function enables a power saving operation by
reducing the cut-out pressure to a preset target value,
based on if the load/unload cycling interval is longer
than the set interval. If the cycling interval time is
longer than set interval, the system reduces the
cut-out pressure to a target so as to make the cycling
interval closer to the set value. Minimum cut-out
pressure is cut-in pressure + 7 psi (0.05 MPa).
Minimum cycle time is 30 seconds.
If the cycle time is 30 seconds or more, SELECT/
WIDE light turns on (blinking) to indicate
ECOMODE is effective. By setting the ECOMODE
to ON, the display’s TYPE field shows SAVE for a
power saving operation. (
3.3.2)
(2) Caution for using ECOMODE
Larger than standard air receiver tank is required to
keep the ECOMODE effective. (
5.4.5 )
Energy Saving Effect
Load Unload
Time
Cut-out
pressure
Cut-in
pressure
Line pressure
Cut-out is
automatically
reduced.
Factorysetting
Pressure differential between cut-in and cut-out pressure: 15 psi (0.1 MPa)
Allowable pressure differential for ECOMODE: 7 psi (0.05 MPa) (unable to change)
Minimum cycle time: 30 seconds
3.4.7 Pressure Setting Switching Function
Two different combinations of cut-out pressure and cut-in
pressures can be used: Pressure combination 1 and 2.
The Combination 1 is used as the standard daily settings.
The Combination 2 is used for a limited time period
where different settings may be required, and can be set
for a certain time (
3.3.5 󱦳 and 3.4.2 for the detail)
Load light turns on (glowing) during load and turns off
during unload when pressure combination 1 is selected.
Load light turns on (blinking) during load and turns off
during unload when pressure combination 2 is selected.
ECOMODE and PQ wide mode is invalid during pressure
combination 2 is activated.
External selection of Cut-in/Cut-out pressure combination
1 or 2 is an option. (F018-2). Contact the local HITACHI
distributor/master dealer or representative office.
ONOFF
External contact (option)
Time
Energy Saving Effect
Load Unload
Glow OFF Glow
Glow
Blink
Blink
BlinkOFF OFF OFF
Cut-out
press.2
Cut-in
press. 2
Cut-out
press.1
Cut-in
press.1
Line pressure
Load light

Other manuals for Hitachi NEXT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi NEXT Series and is the answer not in the manual?

Hitachi NEXT Series Specifications

General IconGeneral
BrandHitachi
ModelNEXT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals