Data just before the latest failure
Contents of Check 2
Press “∨” to go to the next page. Press “∧” to go to the previous page.
Continue from previous page
➪
Temperature Status Display
1 Inlet Air Temperature q1 23 Corresponds to item “b2” in Check 1.
➪
2 Outlet Air Temperature q2 50 Corresponds to item “b3” in Check 1.
➪
3
IDU Heat Exchanger Liquid Piping
(frozen) Temperature
q3 25 Corresponds to item “b4” in Check 1.
➪
4 Outdoor Temperature q4 12 Corresponds to item “b6” in Check 1.
➪
5 Gas Pipe Temp. q5 25 Corresponds to item “b7” in Check 1.
➪
6 Evaporating Temp. at Heating q6 03 Corresponds to item “b8” in Check 1.
➪
7 Control Information q7 -- Corresponds to item “b9” in Check 1.
➪
8 Compressor temperature q8 45 Corresponds to item “bA” in Check 1.
➪
Pressure / Frequency
➪
9 Discharge Pressure q9 18 Corresponds to item “H1” in Check 1. Unit is (×0.1MPa).
➪
10 Inlet Pressure qA 04 Corresponds to item “H2” in Check 1. Unit is (×0.1MPa).
➪
11 Control Information qb 44 Corresponds to item “H3” in Check 1.
➪
12 Operating Frequency (Hz) qC 44 Corresponds to item “H4” in Check 1.
➪
Electronic Expansion Valve
13 IDU Electronic Expansion Valve (%) qd 20
Corresponds to item “L1” in Check 1.
➪
14 ODU Electronic Expansion Valve1 (%) qE 99
Corresponds to item “L2” in Check 1.
➪
Current Value (reference)
15 Compressor Current (A) qF 20
Corresponds to item “P1” in Check 1.