EasyManua.ls Logo

Hitachi PC-ARFG-E - Page 70

Hitachi PC-ARFG-E
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Element Optional function
Individual
setting
Settings Setting conditions Description
rC
Maximum outdoor
temperature to allow
operation mode switch to
heating in auto cooling/
heating with dual set point
X
00 Disabled
If outdoor ambient temperature
is higher than rC, there is no
mode transition to heating
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from cooling to heating.
01 20.0°C
02 21.0°C
03 22.0°C
·
·
·
·
·
·
21 40.0°C
22 0.0°C
23 1.0°C
24 2.0°C
·
·
·
·
·
·
41 19.0°C
rd
Minimum outdoor
temperature to allow
operation mode switch to
cooling in auto cooling/
heating with dual set point
X
00 Disabled
If outdoor ambient temperature
is lower than rd, there is no
mode transition to cooling
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from heating to cooling.
01 10.0°C
02 11.0°C
03 12.0°C
·
·
·
·
·
·
31 40.0°C
32 -20.0°C
33 -19.0°C
34 -18.0°C
·
·
·
·
·
·
61 9.0°C
rE
Temperature for the
beginning of heating in
setback
X
00 15.0°C
If room temperature becomes
lower than this setting, indoor
unit operation is resumed in
heating mode by the setback
function.
01 16.0°C
02 17.0°C
03 18.0°C
04 19.0°C
05 10.0°C
06 11.0°C
07 12.0°C
08 13.0°C
09 14.0°C
rF
Temperature for the
beginning of cooling in
setback
X
00 26.0°C
If room temperature becomes
higher than this setting, indoor
unit operation is resumed in
cooling mode by the setback
function.
01 27.0°C
02 28.0°C
03 29.0°C
04 30.0°C
05 31.0°C
06 32.0°C
07 33.0°C
08 34.0°C
09 35.0°C
10 25.0°C
S1 Not used -
00
- Use at 00 conditions
01
S2 Not used -
00
- Use at 00 conditions
01
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/2022
56

Table of Contents

Other manuals for Hitachi PC-ARFG-E

Related product manuals