Continue from previous page
➪
Abnormality counter
17 Times of abnormality E1 01
➪
18 Times of power failure E2 00
➪
19
Times of abnormal transmitting
(remote controller-outdoor unit)
E3 00
➪
20 Times of inverter tripping E4 00
➪
Control Information Display
➪
21 Control information F1 00
➪
Pressure / Frequency
22 Discharge Pressure H1 18
➪
23 Inlet pressure H2 04
➪
24 Control Information H3 44
➪
25 Operating frequency (Hz) H4 44
➪
Indoor unit capacity / Model / System number display
26 Indoor unit capacity J1 08
➪
27 Outdoor unit model J2 F.01
➪
28 System number J3 01
➪
29 System number J4 00
➪
Continue to next page
This number is incremented when transmission error occurs between
Wired Remote Controller and Indoor units and the error remains for 3
minutes or longer.
For units without high pressure sensor, the value for H1 is a control
information. Unit is (×0.1MPa). Value for unit A is shown for multi-type
units.
For units without high pressure sensor, the value for H2 is a control
information. Unit is (×0.1MPa). Value for unit A is shown for multi-type
units.
Operating frequency of the compressor is shown. (Max. number for this
item is 255) For units without inverter compressor, the value for H4 is a
control information.
J3:01-64 (Set the shipping status of RSW5 to 01 and decimal
representation)
J4:00-3F(Set the shipping status of RSW5 to 00 and hexadecimal
representation)
Code Indoor unit capacity number Equivalent horse power
06 22 0.8
08 28 1.0
10 36 1.3
11 40 1.5
13 45 1.8
14 50 2.0
16 56 2.3
18 63 2.5
Code Indoor unit capacity number Equivalent horse power
20 71 2.8
22 80 3.0
26 90 3.3
32 112 4.0
40 140 5.0
48 160 6.0
64 200 - 224 7.5 - 8.0
80 280 10.0
Model code
Indication Model
H Heat pump
P Inverter
F Multi (SET-FREE)
C Cooling only
E Other
b IVX, individual operation
L KPI
*1: n indicates the quantity of the indoor units that are connected to the
system (n=01-16). “E.00” is shown if communication error is occurred
between indoor units and outdoor units.
*2: For former outdoor units (models before 2010 April), “P” is shown.
Internal information of Wired Remote Controller is shown.
Indoor unit capacity code
The maximum count is 99. (99 is indicated for 99 or more)
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/2022
84