5.3 Control and safety devices
5.3.1 Outdoor unit
Compressor protection
The compressor is protected by the following devices and their combinations:
1. Pressure switch: this switch stops the compressor when the discharge pressure exceeds the set value.
2. Oil
heater: this band-type heater protects against the formation of foam on the oil during cold starts and remains enabled
when the compressor is at a standstill.
Model RAS-(8-12)FSXN RAS-(14-18)FSXN
Compressor
Pressure switches Automatic restart (one per compressor)
High pressure
Disconnection MPa 4.15
-0.05
-0.15
Connection MPa 3.20
±0.15
Fuse capacity (3N~ 400V 50Hz) 40x2 40x2 + 32x2
Oil heater
Power W 40x2 40x4
CCP timer Not adjustable
Time setting min. 3
Direct current module for fan
Fuse capacity A 20x1
5.3.2 CH unit
Model CH-(6.0/10.0)N1
For control circuit
A 5
Fuse capacity on PCB
5 Control system
111
SMGB0065 rev. 1 - 12/2010