EasyManua.ls Logo

Hitachi RAS-10FSXN - Electrical Checks of Main Parts

Hitachi RAS-10FSXN
367 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item Part Name Item Part Name
PCB1 Control PCB in Outdoor unit PCB2 Inverter PCB
IPM Transistor module FANM1 Fan controller
DM Diode module DCL1, 2 Reactor
NF1~15 Noise filter R1, 2 Resistor
RS1, 2 Resistor for starting C Capacitor
CB1 , 2, 3 Capacitor CS1, 2 Capacitor
TB1, 2, 3 Terminal board CMC1, 2 Magnetic contactor for compressor motor
EF1, 2, 3, 4, 11 Fuse EFR1 Fuse on PCB1
CT2, CTU, CTV Current sensor ZNR Surge Absorver
10.16.2 Removing the PCB2 for the inverter
D A N G E R
Turn OFF all the power source switches.
Do
not
touch any electrical component if the LED201 (Red) of the PCB2 is ON. Touching them could cause an
electric shock.
1 Disconnect all the wiring connected to the PCB2 -A-.
2 Disconnect all the power supply lines of the transistor module
-E- (U, V, W) and direct the wiring from the current sensor. Also
disconnect the wiring for N, P and C.
3 Remove the three M3 screws -B-, remove the bushes -C- and
the collars -D- of the PCB2. When fitting the PCB2 make sure
that the bushes and the collars are well fixed.
N O T E
Match the
numbered terminals with the band marked with numbers when reassembling. If they are connected
incorrectly, this may cause a malfunction and damage the electrical components.
Check to ensure that the electrical wiring does not get caught between the electrical components and the
mounting plate when you fit the PCB2.
10.16.3 Removing the diode module and transistor module
D A N G E R
Turn OFF all the power source switches.
Do
not
touch any electrical component if the LED201 (Red) of the PCB2 is ON. Touching them could cause an
electric shock.
A
F
B
C
E
D
A
10 Servicing
325
SMGB0065 rev. 1 - 12/2010
10

Table of Contents

Related product manuals