Alarm code
5C
Abnormal fan controller sensor.
* Activation conditions:
This alarm is indicated when the following conditions occur.
After starting the fan motor operation, the fan controller current does not increase over 1.5 A.
Before starting the fan motor operation, the fan controller peak current does not increase over 4 A.
Check the fan motor.
Restart operation.
Abnormal
Faulty fan controller
and replace
f
an controll
er. *1)
Faulty fan controller
and replace
f
an controll
er. *1)
Fan motor stops
immedi
ately
.
Fan motor is not operated.
How is fan motor
operation when
restar
ted?
Is the fan motor coil
nor
mal?
Nor
mall
*1): Carry out the electrical discharge when fan controller is checked or replaced, refer to: Checking procedures
for other
main parts, see on page 267.
8 Troubleshooting
231
SMGB0065 rev. 1 - 12/2010