6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
209
6
6.2  Optional functions through Remote control
The next list refers to the optional functions available to indoor units from the remote control switch. Note that not all 
remote control switch have access to all the optional functions. Check the Technical Catalogue for Indoor units remote 
controls.
6.2.1  List of optional remote control functions. (PC-ARFPE)
Elem. Optional function
Individual 
setting
Settings Setting conditions Description
b1
Correction of setting 
temperature in heating
Models: 
RCD-FSN3 
RCIM-FSN4(E)
O
00
Normal (Setting Temperature + 
4ºC)
This function is used to adjust the 
difference of temperature between 
the setting temperature of the remote 
control switch and the inlet air 
temperature of the indoor unit.
This is useful when the inlet air 
thermistor is not placed inside the 
indoor unit.
01 Release (Setting Temperature)
02 Setting Temperature + 2ºC
03 Setting Temperature + 3ºC
04 Setting Temperature + 1ºC
Correction of setting 
temperature in heating
Models: 
RPI-FSN3(P)E 
RPC-FSN3E 
RPF(I)-FSN2E 
RPI-FSN4E 
RPIM-FSN4E(-DU)
O
00
Normal (Setting Temperature 
+ 4ºC or Setting temperature + 
2ºC)
Standard setting. It increases the 
temperature +4ºC
01
Release (Setting Temperature)
Removal
02
Setting Temperature + 2ºC 
Increases the temperature +2ºC 
(1)
.
Correction of setting 
temperature in heating
Models: 
RCI-FSN4  
RPC-FSN3 
RPK-FSN3M
O
00
Normal (Setting Temperature + 
4ºC 
Standard setting. Increases the 
temperature +4ºC
01
Release (Setting Temperature)
Removal
02
Setting Temperature + 2ºC
It increases the temperature 
+2ºC 
(1)
.
b2
Circulator function at 
heating Thermo-OFF
O
00 Not activated function
This function means that the fan 
unit remains running after the air 
conditioning system has stopped 
to prevent the air in the room from 
stratifying.
01 Activated function
b3
Forced compressor 
operation for at least 
three minutes through C7 
setting 
O
00
Not activated function 
(C7 setting possible)
This function is used to allow 
the setting of C7: protect the  
compressor, preventing it from being 
started or stopped for periods of less 
than three minutes.
Not available for models: 
RCIM-FSN4(E) 
RCD-FSN3
01
Activated function 
(C7 setting not possible)
b4
Change the lter cleaning 
period.
O
00 Standard (1200 h factory setting)
This function is used to modify the 
period during which the remote 
control indicates the air lter 
replacement.
01 100 hours
02 1200 hours
03 2500 hours
04 No indication
b5 Fixing of operation mode X
00 Not activated function Once the unit operating mode has 
been selected, this function prevents 
it from being modied from the 
remote control.
01 Activated function
b6
Fixing of setting 
temperature
X
00 Not activated function
Once the unit temperature has been 
selected, this function prevents from 
being modied from the remote 
control.
01 Activated function