2 Unit installation
RPI - Ducted indoor unit (8/10)FSN3E(-f)
SMGB0099 rev.0 - 12/2016
55
2
2.6.3  Air duct connection
? NOTE
•  Use eld-supplied exible ducts to avoid abnormal acoustic vibrations.
•  RPI units are supplied with a standard air lter on the suction side. This lter is supplied for cases where no suction duct is applied (or 
when the duct is very short).
Secure the exible air duct to the outsides of the hoses supplied with the unit.
Bear in mind the following instructions depending on the installation type:
1  Where the suction duct is not used, keep the standard air lter.
2  Where the suction duct is used, t the air lter at the suction duct 
inlet point, removing the standard air lter from the unit. This air 
lter must be eld-supplied or a factory-adapted one must be 
used.
Outlet air
Inlet air
Air lter (eld supplied)
Outlet air
Inlet air
Air lter
Damper  
(eld supplied)
Air lter  
(eld supplied)
Insulated duct (installed on the 
outer side of the anges)
Flexible duct installation  
(rubber or textil material)
2.6.4  Maintenance of the suction air lter
Simply remove the set screws from the bar -1- (4 screws) and remove it to pull the lter downwards.
2
1