When selecting multi-step speed running, the
multi-step speed is within the range of -fmax–
fmax, and it can be set continuously. The
start/stop of multi-step stop is also determined by
P00.01.
S1 series inverter can set 16-step speed, which
are set by combined codes of multi-step terminals
1–4 (set by S terminal, correspond to function
code P05.01–P05.06) and correspond to
multi-step speed 0 to multi-step speed 15.
When terminal 1, terminal 2, terminal 3 and
terminal 4 are OFF, the frequency input mode is
set by P00.06 or P00.07. When terminal 1,
terminal 2, terminal 3 and terminal 4 are not all
OFF, the frequency set by multi-step speed will
prevail, and the priority of multi-step setting is
higher than that of the keypad, analog,
high-speed pulse, PID, and communication
settings.
The relation between terminal 1, terminal 2,
terminal 3 and terminal 4 are shown in the table