S1 series standard inverter
-67-
AI1
HDIB
P05.24
P05.25
P05.26
P05.27
P05.39
P05.40
P05.41
P05.42
P05.45
P05.46
P05.47
P05.48
P05.43
P05.28
P05.49
P17.19
P17.22
AI2
P05.29
P05.30
P05.31
P05.32
P05.33
P05.34
P05.35
P05.36
P05.37
P17.20
P05.00
HDIB input type
0
1
1
2
0
P05.44
(HDIB high-speed pulse input function
selection)
AI1 input voltage
AI2 input voltage
HDIB input frequency
AI1/AI2/HDI
P05.00
Ones
0: HDIA is high-speed pulse input
1: HDIA is digital input
P05.38
0: Set input via frequency
1: Reserved
2: Input via encoder
Analog input curve setting
Analog input filter
P05.00
Tens
0: HDIB is high-speed pulse input
1: HDIB is digital input
P05.44
0: Set input via frequency
1: Reserved
2: Input via encoder
HDIA
P17.21
0
1
1
2
0
P05.38
(HDIA high-speed pulse input function
selection)
HDIA input frequency
P05.00
HDIA input type
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P05.00
HDI input type
0x000x11
Ones: HDI/HDIA input type
0: HDI/HDIA is high-speed pulse input
1: HDI/HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0x00
P05.24
Lower limit value of AI1
0.00VP05.26
0.00V
P05.25
Corresponding setting of
lower limit of AI1
-100.0%100.0%
0.0%
P05.26
Upper limit value of AI1
P05.2410.00V
10.00V
P05.27
Corresponding setting of
upper limit of AI1
-100.0%100.0%
100.0%
P05.28
Input filter time of AI1
0.000s10.000s
0.100s
P05.29
Lower limit value of AI2
-10.00VP05.31
-10.00V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi S1 Series and is the answer not in the manual?

Hitachi S1 Series Specifications

General IconGeneral
Output Frequency0 - 400 Hz
Overload Capacity150% for 60 seconds
Frequency50/60 Hz
Control MethodSensorless Vector Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS485, Modbus RTU
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC (Matches Input Voltage)
Cooling MethodFan Cooled