4-30
Chapter 4
For parameter configuration
[bC210] to [bC225]
(Example 2)
When [bC111]=01, Inverter rated current:64A[bC110]=64(A),
Base frequency [Hb103]=60Hz, Output frequency=2.5Hz
In case of output frequency = 2.5Hz, the reduction scale
is x0.9, then, the inverter will trip when the output
current of 135%(=150%×0.9) flows continuously within
60s according to the curve.
(Example 3) When [bC111] = 02, and Output frequency = [bC122]
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
bC210 Electronic thermal level setting,
2nd-motor
Same as bC110
bC211 Electronic thermal characteristic
selection, 2nd-motor
Same as bC111
bC212 Electronic thermal decrease function
selection, 2nd-motor
Same as bC112
bC213 Electronic thermal decreasing time,
2nd-motor
Same as bC113
bC220 Free electronic thermal frequency-1,
2nd-motor
Same as bC120
bC221 Free electronic thermal current-1,
2nd-motor
Same as bC121
bC222 Free electronic thermal frequency-2,
2nd-motor
Same as bC122
bC223 Free electronic thermal current-2,
2nd-motor
Same as bC123
bC224 Free electronic thermal frequency-3,
2nd-motor
Same as bC124
bC225 Free electronic thermal current-3,
2nd-motor
Same as bC125
[bd-01] to [bd-04]
Functional Safety terminal (STO) *1
Code/Name
Range (unit)
Initial
value
bd-01 STO input display
selection
00(Warning(display))/
01(Warning(without
display))/02(Trip)
00
bd-02 STO input change time
0.00 to 60.00(s)
1.00
bd-03 Display selection during
STO input change time
00(Warning(display))/
01(Warning(without
display))
00
bd-04 Action selection after
STO input change time
00(Maintain current
status)/
01(Disable)/02(Trip)
00
*1) SH1 series dont support safety function.
For more information, Please contact your supplier or local Hitachi
inverter sales office.
Notes on electronic thermal function !
The SH1 is implemented with the inverter-protected
electronic thermal (not user-configurable) separately
the Electronic thermal protection for the motor.
It operates as an electronic thermal with 150% ND
rated current and the constant torque characteristics
regardless of the setting of [Ub-03] Load type selection.
(Refer to the left (Example 2) ).
Even if [Ub-03] is changed to “Low Duty (LD)” or “Very
Low Duty (VLD)”, check the carrier derating at the
“Normal Duty” rating.
In some cases, E039 Controller (inverter) overload
occurs.
For more information, Please contact your supplier or
local Hitachi inverter sales office.
Maximum frequency (Hz)
[Hb105][Hd105]
[bC125]
[bC123]
[bC125]
[bC120]
[bC122]
[bC124]
0
Current
output (A)
Trip time (s)
60
3.0
(x)
(y)
(z)
0
Output current (A)
(x)[bC123]×109% (y)[bC123]×150% (z)[bC123]×200%
Reduction
scale
Inverter output
frequency (Hz)
X1.0
0
60
X0.9
X0.8
5
2.5
62.8
(98.1%)
86.4
(135%)
115.2
(180%)
Motor current (A)
(Ratio to the inverter
rated current)
60
3.0
0
Trip time(s)