For parameter configuration
[CC-20] to [CC-33]
Output terminals stabilization
CC-20 Output terminal [11] on-delay time
CC-21 Output terminal [11] off-delay time
CC-22 Output terminal [12] on-delay time
CC-23 Output terminal [12] off-delay time
CC-24 Output terminal [13] on-delay time
CC-25 Output terminal [13] off-delay time
CC-26 Output terminal [14] on-delay time
CC-27 Output terminal [14] off-delay time
CC-28 Output terminal [15] on-delay time
CC-29 Output terminal [15] off-delay time
CC-30 Output terminal [16] on-delay
time*1)
CC-31 Output terminal [16] off-delay
time*1)
CC-32 Output terminal [AL] on-delay time
CC-33 Output terminal [AL] off-delay time
・The above parameters set the delay time from the
change of the output terminal to the actual response.
*1) SH1 series do not have this terminal.
[Output terminal function list]
ON while output is active
Constant-frequency
reached
Turns ON when the output
frequency reaches and
same as frequency
reference and stable.
Set frequency
overreached
Turns ON when the output
frequency exceeds the
specified arrival value.
[CE-10][CE-11]
Turns ON when the output
frequency is the same
(within the fixed narrow
range) as the set value.
[CE-10][CE-11]
Set frequency
overreached 2
Same as FA2. The setting is
based on [CE-12] [CE-13].
Same as FA3. The setting is
based on [CE-12] [CE-13].
ON when inverter is ready
ON while in forward drive
ON while in reverse drive
Frequency reference
= Keypad is selected
ON if the frequency
reference is from keypad
Run command =
Keypad is selected
ON if the RUN command is
from keypad.
(For future. Do not assign.)
ON if major failure trips
ON if torque exceeds the
level [CE120] to [CE123].
Instantaneous
power failure
After the main power
supply R,S,T is established,
it turns ON when an
instantaneous power
failure of the main power
supply is detected.
Turns on when main
power drops or control
power fails.
ON if torque limit operates
IP-Non stop function
is active
ON if IP-Non stop function
operates in power loss.
Accumulated
operation time over
ON if set time [CE-36] is
exceeded
Accumulated
power-on time over
ON if set time [CE-36] is
exceeded
Electronic thermal
alarm signal(MTR)
ON if motor thermal
integral value exceeds set
value [CE-30]
Electronic thermal
alarm signal(CTL)
ON if inverter thermal
integral value exceeds set
value [CE-31]
Heat sink overheat
warning
ON when the heatsink
temperature is over the
setting value [CE-34].
Low-current
indication signal
ON if output current is less
than the setting value
[CE102].
*1) This function is disabled when the Control mode selection
[AA121/AA221] setting is 00 to 07 (V/f control mode).