For  parameter  configuration 
[CE101] to [CE107] 
  Low-current detection signal 
CE101 Low current 
signal output mode 
selection, 1st motor 
00(During Accel/Decel and 
constant speed) 
01(During constant speed 
only) 
CE102 
Low current detection 
level 1, 1st motor 
Inverter rated 
current×(0.00 to 2.00)(A) 
Inverter 
rated current 
×1.00(A) 
CE103 
Low current detection 
level 2, 1st motor 
Inverter rated 
current×(0.00 to 2.00)(A) 
Inverter 
rated current 
×1.00(A) 
・When the output current is lower than the set value, output 
terminal 033[LOC]/034[LOC2] Low-current indication signal 
1/2 Outputs low current signal. 
 
 
  Overload detection signal 
CE105 
Overload  signal  output 
mode  selection,  1st 
motor 
00(During  Accel/Decel 
and constant speed)/ 
01(During  constant 
speed only) 
CE106 Overload 
warning level 1, 1st 
motor 
Inverter rated 
current×(0.00 to 2.00)(A) 
Inverter 
rated current 
×1.00(A) 
CE107 Overload 
warning level 2, 1st 
motor 
Inverter rated 
current×(0.00 to 2.00)(A) 
Inverter 
rated current 
×1.00(A) 
・When overload occurs, Output terminal 
035[OL]/036[OL2] overload notice advance signals are 
output. 
 
 
[CE-10] to [CE-31] 
  Frequency arrival signal 
CE-10 Arrival frequency 1 value setting 
during acceleration 
CE-11 Arrival frequency 1 value setting 
during deceleration 
CE-12 Arrival frequency 2 value setting 
during acceleration 
CE-13 Arrival frequency 2 value setting 
during deceleration 
・Above parameters set the operation of the frequency 
arrival signal. 
 
(Example) In 003[FA2]/005[FA4] case: 
 
(Example) In 004[FA3]/006[FA5] case: 
 
 
  Over-torque signal 
CE120 Over-torque level (Forward 
drive), 1st motor 
CE121 Over-torque level (Reverse 
regenerative), 1st motor 
CE122 Over-torque level (Reverse 
drive), 1st motor 
CE123 Over-torque level (Forward 
regenerative), 1st motor 
・Sets the level to output the 019[OTQ] signal, when using 
vector control and the torque goes over the limit. 
 
  Electronic thermal warning 
CE-30 Electronic thermal warning level 
(MTR) 
CE-31 Electronic thermal warning level 
(CTL) 
・[CE-30] sets the level to output the motor electronic 
thermal warning 026[THM]. 
・[CE-31] sets the level to output the inverter electronic 
thermal warning 027[THC]. 
fon:Maximum frequency 1% 
foff:Maximum frequency 2% 
fon:Maximum frequency 1% 
foff:Maximum frequency 2% 
Overload warning 
level [CE106]/[CE107] 
Low-current 
indication signal 
detection level 
[CE102]/[CE103] 
[LOC]/[LOC2] 
indication signal