For  parameter  configuration 
[CE-33] to [CE-51] 
  0Hz speed detection signal   
CE-33 Zero speed detection level 
・Set the level in which the output terminal 040[ZS] Zero 
speed detection turns ON. 
 
  Cooling fin overheat warning signal 
CE-34 Cooling fin overheat 
warning level 
・Set the level in which output terminal 032[OHF]Heat 
sink overheat warning turns ON. 
 
  Accumulated RUN time /   
Accumulated PowerON time warning 
CE-36 Accum. RUN time (RNT) / 
Accum. Power-On time (ONT) setting   
・Set the warning level in which the output terminal 
024[RNT] accumulated operation time over and output 
terminal 025[ONT] accumulated power-on time over 
turn ON. 
 
  Window comparator (detection of terminal 
disconnection) 
CE-40 [Ai1] Window 
comparator higher limit 
CE-41 [Ai1] Window 
comparator lower limit 
CE-42 [Ai1] Window 
comparator hysteresis width 
CE-43 [Ai2] Window 
comparator higher limit 
CE-44 [Ai2] Window 
comparator lower limit 
CE-45 [Ai2] Window 
comparator hysteresis width 
CE-46 [Ai3] Window 
comparator higher limit 
CE-47 [Ai3] Window 
comparator lower limit 
CE-48 [Ai3] Window 
comparator hysteresis width 
CE-50 [Ai1] Operation set level 
at disconnection or compare 
event 
CE-51 [Ai1] Operation set level 
implement timing 
00(Disable)/ 
01(Enable(at 
WC*active)/ 
02(Enable(at 
WC*de-active) 
[CE-52] to [CE-55][CE201]to[CE223] 
CE-52 [Ai2] Operation set level 
at disconnection or compare 
event 
CE-53 [Ai2] Operation set level 
implement timing 
00(Disable)/ 
01(Enable 
(at WC*active)/ 
02(Enable 
(at WC*de-active) 
CE-54 [Ai3] Operation set level 
at disconnection or compare 
event 
CE-55 [Ai3] Operation set level 
implement timing 
00(Disable)/ 
01(Enable 
(at WC*active)/ 
02(Enable 
(at WC*de-active) 
・Window comparator function output signals whenever the 
analog inputs value are within or out of range. 
・In the case of disconnection judgment, the reference value 
can be set to the [CE-50]/[CE-52]/[CE-54] setting value 
when it is within or out of the range of the window 
comparator. 
 
If in case [CE-51] [CE-53] [CE-55] = 02:   
 
 
  2nd motor When Intelligent Input terminal 024[SET] is enabled. 
CE201 Low current signal output mode 
selection, 2nd-motor 
CE202 Low current detection level 1, 
2nd-motor 
CE203 Low current detection level 2, 
2nd-motor 
CE205 Overcurrent signal output mode 
selection, 2nd-motor 
CE206 Overcurrent detection level 1, 
2nd-motor 
CE207 Overcurrent detection level 2, 
2nd-motor 
CE220 Over-torque level (Forward 
drive), 2nd-motor 
CE221 Over-torque level (Reverse 
regenerative), 2nd-motor 
CE222 Over-torque level (Reverse 
drive), 2nd-motor 
CE223 Over-torque level (Forward 
regenerative), 2nd motor 
Min 
(Ai1/Ai2:0%) 
(Ai3:-100%) 
Analog operation level 
at disconnection 
CE-50/CE-52/CE-54 
 
Maximum-limit level   
of window comparator 
CE-40/CE-43/CE-46 
Minimum-limit level of 
window comparator 
CE-41/CF-44/CF-47 
 
Hysteresis width 
[CE-42]/[CE-45]/[CE-48]