4-48
Chapter 4
For parameter configuration
[Hd202] to [Hd237]
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
Perm. Magnet Sync. Motor (SM/PMM)
Hd202
Sync. Motor capacity setting, 2nd-motor
Same as Hd102
Hd203
Sync. Motor number of poles setting,
2nd-motor
Same as Hd103
Hd204 Sync. Base frequency setting,
2nd-motor
Same as Hd104
Hd205 Sync. Maximum frequency setting,
2nd-motor
Same as Hd105
Hd206 Sync. Motor rated voltage,
2nd-motor
Same as Hd106
Hd208 Sync. Motor rated current,
2nd-motor
Same as Hd108
Hd210 Sync. Motor constant R,
2nd-motor
Same as Hd110
Hd212 Sync. Motor constant Ld,
2nd-motor
Same as Hd112
Hd214 Sync. Motor constant Lq,
2nd-motor
Same as Hd114
Hd216 Sync. Motor constant Ke,
2nd-motor
Same as Hd116
Hd218 Sync. Motor constant J,
2nd-motor
Same as Hd118
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
Hd230 Minimum frequency adjustment for
Sync.M, 2nd-motor
Same as Hd130
Hd231 No-Load current for Sync.M,
2nd-motor
Same as Hd131
Hd232 Starting method for Sync.M,
2nd-motor
Same as Hd132
Hd233 IMPE 0V wait number for Sync.M,
2nd-motor
Same as Hd133
Hd234 IMPE detect wait number for Sync.M,
2nd-motor
Same as Hd134
Hd235 IMPE detect number for Sync.M,
2nd-motor
Same as Hd135
Hd236 IMPE voltage gain for Sync.M,
2nd-motor
Same as Hd136
Hd237 IMPE Mg-pole position offset,
2nd-motor
Same as Hd137
[oA-10] to [oA-33][ob-01] to [ob-04]
Parameter mode (o code)
”o” parameters are displayed by the [UA-22] = 01. This
configuration is not necessary except when option is used.
The implementation of the following parameters might differ
depending on the type of option being used.
For more information, please contact your supplier or
local Hitachi inverter sales office.
Optional cassette error operation
Code/Name
Range (unit)
Initial
value
oA-10 Operation selection at
an option error (SLOT-1)
00(Error)/
01((Ignore error
(keep running))
00
oA-11 Communication
Watch Dog Timer (SLOT-1)
0.00 to 100.00(s)
1.00
oA-12 Action selection at a
communication error (SLOT-1)
00(Error)/
01(Trip after Deceleration
stop)/02(Ignore)/
03(Free run stop)/
04(Deceleration stop)
01
oA-13 RUN command
selection at start up (SLOT-1)
00(Disable)/
01(Enable)
00
oA-20 Operation selection at
an option error (SLOT-2)
00(Error)/
01((Ignore error
(keep running))
00
oA-21 Communication
Watch Dog Timer (SLOT-2)
0.00 to 100.00(s)
1.00
oA-22 Action selection at a
communication error (SLOT-2)
00(Error)/
01(Trip after Deceleration
stop)/
02(Ignore)/
03(Free run stop)/
04(Deceleration stop)
01
oA-23 RUN command
selection at start up (SLOT-2)
00(Disable)/
01(Enable)
00
oA-30 Operation selection at
an option error (SLOT-3)
00(Error)/
01((Ignore error
(keep running))
00
oA-31 Communication
Watch Dog Timer (SLOT-3)
0.00 to 100.00(s)
1.00
oA-32 Action selection at a
communication error (SLOT-3)
00(Error)/
01(Trip after Deceleration
stop)/02(Ignore)/
03(Free run stop)/
04(Deceleration stop)
01
oA-33 RUN command
selection at start up (SLOT-3)
00(Disable)/
01(Enable)
00
In P1-CCL CC-Link communication option, there are no
dedicated parameters other than the above parameters.
For more information, please contact your supplier or
local Hitachi inverter sales office.
P1-FB Encoder Feedback Option setting
Code/Name
Range (unit)
Initial
value
ob-01 Encoder constant
setting (option)
32 to 65535(pls)
1024
ob-02 Encoder phase
sequence selection (option)
00(Phase-A Lead)/
01(Phase-B Lead)
0
ob-03 Motor gear ratio
numerator (option)
1 to 10000
1
ob-04 Motor gear ratio
denominator (option)
1 to 10000
1
Above parameters set the main encoder input and the motor
gear ratio involved in the encoder feedback for the P1-FB.

Related product manuals