4-50
Chapter 4
For parameter configuration
[oE-35] to [oE-49]
P1-AG Analog Input/Output Option
Window comparator output condition
Code/Name
Range (unit)
Initial
value
oE-35 [Ai4] Window
comparator upper limit
0 to 100(%)
100
oE-36 [Ai4] Window
comparator lower limit
0 to 100(%)
0
oE-37 [Ai4] Window
comparator hysteresis width
0 to 10(%)
0
oE-38 [Ai5] Window
comparator upper limit
0 to 100(%)
100
oE-39 [Ai5] Window
comparator lower limit
0 to 100(%)
0
oE-40 [Ai5] Window
comparator hysteresis width
0 to 10(%)
0
oE-41 [Ai6] Window
comparator upper limit
-100 to 100(%)
100
oE-42 [Ai6] Window
comparator lower limit
-100 to 100(%)
-100
oE-43 [Ai6] Window
comparator hysteresis width
0 to 10(%)
0
oE-44 [Ai4] Temporal
operation level set at
disconnection or compare event
0 to 100(%)
0
oE-45 [Ai4] Temporal
operation level implementation
timing
00(Disable)/
01(Enable: At WC*
is active)/
02(Enable: At WC*
is not active)
00
oE-46 [Ai5] Temporal
operation level set at
disconnection or compare event
0 to 100(%)
0
oE-47 [Ai5] Temporal
operation level implementation
timing
00(Disable)/
01(Enable: At WC*
is active)/
02(Enable: At WC*
is not active)
00
oE-48 [Ai6] Temporal
operation level set at
disconnection or compare event
-100 to 100(%)
0
oE-49 [Ai6] Temporal
operation level implementation
timing
00(Disable)/
01(Enable: At WC*
is active)/
02(Enable: At WC*
is not active)
00
Window comparator function output signals whenever
the analog value inputs are within or out of range.
In the case of disconnection judgment, the reference
value can be set to the [oE-44]/[oE-46]/[oE-48] setting
value when it is within or out of the range of the
window comparator.
[oE-50] to [oE-70] [oH-01] to[oH-06]
P1-AG Analog Input/Output Option
Analog output terminal adjustment
Code/Name
Range (unit)
Initial
value
oE-50 [Ao3] Output monitor
selection
Set monitor code
dA-01
oE-51 [Ao4] Output monitor
selection
dA-01
oE-52 [Ao5] Output monitor
selection
dA-01
oE-56 [Ao3] Output filter time
constant
1 to 500(ms)
100
oE-57 [Ao3] Data type
selection
00(Absolute value)/
01(Signed value)
00
oE-58 [Ao3] Bias adjustment
-100.0 to 100.0(%)
100.0
oE-59 [Ao3] Gain adjustment
-1000.0 to
1000.0(%)
100.0
oE-60 Adjustment mode [Ao3]
output level
-100.0 to 100.0(%)
100.0
oE-61 [Ao4] Output filter time
constant
1 to 500(ms)
100
oE-62
[Ao4] Data type selection
00(Absolute value)/
01(Signed value)
00
oE-63 [Ao4] Bias adjustment
-100.0 to 100.0(%)
0.0
oE-64 [Ao4] Gain adjustment
-1000.0 to
1000.0(%)
100.0
oE-65 Adjustment mode [Ao4]
output level
-100.0 to 100.0(%)
100.0
oE-66 [Ao5] Output filter time
constant
1 to 500(ms)
100
oE-67 [Ao5] Data type
selection
00(Absolute value)/
01(Signed value)
00
oE-68 [Ao5] Bias adjustment
-100.0 to 100.0(%)
0.0
oE-69 [Ao5] Gain adjustment
-1000.0 to
1000.0(%)
100.0
oE-70 Adjustment mode [Ao5]
output level
-100.0 to 100.0(%)
100.0
Regarding the adjustment method of the analog
input/output option, contact your supplier or local Hitachi
inverter sales office for more information.
P1-EN Ethernet communication Option setting
Code/Name
Range (unit)
Initial
value
oH-01 IP-address
selection(P1-EN)
00(Group 1)/
01(Group 2)
00
oH-02 Communication speed
(port-1) (P1-EN)
00(Auto-negotiation)/
01(100M:full duplex)/
02(100M:half duplex)/
03(10M:full duplex)/
04(10M:half duplex)
00
oH-03 Communication speed
(port-2) (P1-EN)
00
oH-04 Ethernet communication
timeout(P1-EN)
1 to 65535(×10ms)
3000
oH-05
Modbus TCP Port No.(IPv4) (P1-EN)
502, 1024 to 65535
502
oH-06
Modbus TCP Port No.(IPv6) (P1-EN)
502, 1024 to 65535
502