For  parameter  configuration 
[UA-90]to[UA-94][Ub-01]to[Ub-05]
[UC-01] 
  MOP keypad setting 
UA-90 
Waiting time for turning off 
the display(MOP) 
UA-91 
Initial  display  selection 
(MOP) 
(Select from d----,   
F---- parameters) 
UA-92   
Enable auto-return to the 
initial display (MOP) 
UA-93 
Enable frequency changes 
through monitor 
display(MOP) 
UA-94   
Enable multi-speed 
frequency changes through 
monitor display (MOP) 
・Above parameters set the behavior of the MOP keypad. 
 
  Initialize 
Ub-01 Initialize 
mode selection 
00(Disable)/ 
01(Error history clear)/ 
02(Data initialize)/ 
03(Error history clear & Data 
initialize)/ 
04(Error history clear & Data 
initialize & EzSQ clear)/ 
05(All data except terminal 
configuration)/ 
06(All data except 
communication 
configuration) 
07(All data except terminal & 
communication 
configuration)/ 
08(EzSQ only) 
Ub-02 Initialize 
data selection 
00(JP)/01(EU)/ 
02(US)/03(CHN) 
00(JPN) 
01(EU) 
02(USA) 
03(CHN) 
Ub-03   
Load type selection 
00(Very Low Duty)/ 
01(Low Duty)/ 
02(Normal Duty) 
Ub-05 Enable 
initialization 
00(Disable)/ 
01(Execute initialization) 
・How to initialize; at first select the initial mode at [Ub-01], next, 
when [Ub-05] is set to 1, initialize process is start. 
・Once setting the load type selection [Ub-03], the inverter load 
rating will be changed instantaneously. 
・SH1-03410-H(SH1-1600H) ~ SH1-04810-H(SH1-2200H) support 
only normal duty(ND) and low duty (LD). 
 
  Factory setting 
 
[Ud-01] to [Ud-37] 
  Trace function 
Ud-01 Trace function enable 
Ud-03 Number of trace data setting 
Ud-04 Number of trace signals setting 
Ud-10 Trace data 0 selection 
(parameters of 
the d**** and 
F**** mode) 
Ud-11 Trace data 1 selection 
Ud-12 Trace data 2 selection 
Ud-13 Trace data 3 selection 
Ud-14 Trace data 4 selection 
Ud-15 Trace data 5 selection 
Ud-16 Trace data 6 selection 
Ud-17 Trace data 7 selection 
Ud-20 Trace signal 0 input/output 
selection 
00(Input:[Ud-21
])/01(Output: 
[Ud-22]) 
Ud-21 Trace signal 0 input terminal 
selection 
Ud-22 Trace signal 0 output terminal 
selection 
Ud-23 Trace signal 1 input/output 
selection 
00(Input:[Ud-24
])/01(Output: 
[Ud-25]) 
Ud-24 Trace signal 1 input terminal 
selection 
Ud-25 Trace signal 1 output terminal 
selection 
Ud-26 Trace signal 2 input/output 
selection 
00(Input:[Ud-27
])/01(Output: 
[Ud-28]) 
Ud-27 Trace signal 2 input terminal 
selection 
Ud-28 Trace signal 2 output terminal 
selection 
Ud-29 Trace signal 3 input/output 
selection 
00(Input:[Ud-30
])/01(Output: 
[Ud-31]) 
Ud-30 Trace signal 3 input terminal 
selection 
Ud-31 Trace signal 3 output terminal 
selection 
Ud-32 Trace signal 4 input/output 
selection 
00(Input:[Ud-33
])/01(Output: 
[Ud-34]) 
Ud-33 Trace signal 4 input terminal 
selection 
Ud-34 Trace signal 4 output terminal 
selection 
Ud-35 Trace signal 5 input/output 
selection 
00(Input:[Ud-36
])/01(Output: 
[Ud-37]) 
Ud-36 Trace signal 5 input terminal 
selection 
Ud-37 Trace signal 5 output terminal 
selection 
*1) Trace start is also possible from ON of input terminal 108[DTR] or 
from ProDriveNext. And while the inverter is in trace function, the 
output terminal 079[TRA] turns ON. 