9
Error Codes
The SJ100 series inverters will trip on over-current, over-voltage,
and under-voltage to protect the inverter. The motor output turns
OFF, allowing the motor to free-run to a stop. Press the Stop/Reset
key to reset the inverter and clear the error.
Basic Error Codes
Error
Code
Name Probable Cause(s)
E01
Over current event while
at constant speed
Inverter output was short-circuited
Motor shaft is locked
Load is too heavy
A dual-voltage motor is wired
incorrectly
Note: The SJ100 will over current trip
at nominally 200% of rated current
E02
Over current event during
deceleration
E03
Over current event during
acceleration
E04
Over current event for
other conditions
DC braking power(A_54) set too
high
Current transformer / noise error
E05
Overload protection Motor overload is detected by the
electronic thermal function
E06
Braking resistor overload Regenerative braking resistor
exceeds the usage time or usage ratio
E07
Over voltage protection DC bus voltage exceeds a threshold,
due to regenerative energy from motor
E08
EEPROM error Built-in EEPROM memory experi-
enced noise, high temperature, etc.
E09
Under-voltage error DC bus voltage decreased enough to
cause a control circuit fault
E10
CT error
(current transformer)
High electrical noise near inverter
A fault occurred in the built-in CT
E11
E22
CPU error Built-in CPU had internal error
E12
External trip [EXT] input signal detected
E13
USP (Unattended Start
Protection)
When (USP) was enabled, an error
occurred when power was applied
while a Run signal was present
E14
Ground fault A ground fault was detected
between the inverter output and the
motor. This feature protects the
inverter, and does not protect humans.