[3] Rectifier Measurement
This is to measure 6 rectifiers of the input side.
Resistance Measurement
Allowable Value
From
To
R(Ll)
S(L2)
50kohm or more
S(L2)
R(Ll)
S(L2)
T(L3)
T(L3)
S(L2)
T(L3)
R(Ll)
R(Ll)
T(L3)
R(Ll)
R(Ll)
S(L2)
S(L2)
T(L3)
T(L3)
Each R(Ll), S(L2) and
T(L3)
-
50kohm or more
-
Each R(Ll), S(L2) and
T(L3)
50 ohm or less
Each R(Ll), S(L2) and
T(L3)
P1
50 ohm or less
P1
Each R(Ll), S(L2) and
T(L3)
50kohm or more
To make sure MOV, visual check of MOV is necessary on the ISPM.
If the result is out of its spec, replace the unit. ( relative check is important )
MOV(ZNR);ZNR1,ZNR2,ZNR3 are for phase to phase