10-4. kW setup procedure
To set up kW, we advise you not to use DOP/DRW !, use only standard panel.
Meaning
set C91 "01" ; Debug on
set C94 "D000" ; kW address
set C95 "xx" ; kW code
set B84 "01" ; to execute FACTORY SETTING
Try FACTORY SETTING
Check B12' display (F-23 E-THM LVL)
B12's display table
kW | 200V | 400V
002 | 1.40 | ----
004 | 2.60 | 1.50
005,007 | 4.00 | 2.50
011,015 | 7.10 | 3.80
022 | 10.00 | 5.50
030,040 | 15.90 | 8.60
055 | 24.0 | 13.0
075 | 32.0 | 16.0
kW code table (common L100/SJ100)
xx | kW
01 | 002
02 | 004
03 | 005,007
04 | 011,015
05 | 022
06 | 030,040
07 | 055
08 | 075
In case of L100, SJ100, it automatically detects it's voltage class with hardware in the ISPM, voltage class
setup is not necessary.
10-15