2  Features and benets
Eco-Desing and Seasonal Efciency
TCGB0136 rev.1 - 05/2021
20
Seasonal Energy Efciency Ratio (SEER) in cooling and the Seasonal Coefcient of Performance (SCOP) in
heating give a more accurate estimation of the real performance of the equipment during the whole period of usage, all 
while considering:
•  Several points of measure (In cooling mode: an outside temperature of 20ºC, 25ºC, 30ºC and 35ºC; in heating mode: 
an outside temperature of +12ºC, +7ºC, +2ºC, and -7ºC.
•  Different compressor speeds (full load and partial load), auxiliary consumption (crankcase heaters, thermostat off 
mode, OFF mode…).
•  Conditions of temperature (number of hours per outdoor temperature) for an identied climate (average climate for 
ErP compliance)
•  Building heat load (called Pdesign)
Hitachi, in compliance with the Eco Design Directive, has developed the new outdoor units: new UTOPIA series, whose 
high efciency level (including SEER and SCOP values) is properly informed to our customers to allow for an easy 
selection.
New UTOPIA series offer high seasonal efciencies, as well as complete exibility, with all outdoor units from both ranges 
being fully compatible with the System Free range of indoor units. Hitachi’s UTOPIA technology has all the benets of 
VRF, including individual control of each indoor unit with an increased number of indoor unit combinations in addition to 
delivering excellent part-load efciency.
With cooling capacities and heating capacities from 2HP to 12HP, a maximum of 4 indoor units are connectable 
to a single outdoor unit, with individual control and efciencies achieved as high as A++/A+ (depending on model/
combinations).
2.2.3 Energy classes and energy label (Lot 10)
The energy efciency classes from A+++ to D are introduced based on SCOP and SEER values: The scale for energy 
labelling is:
A+++
A++
D
C
B
A
A+
E
F
G SCOP < 1,90
1,90SCOP< 2,20
2,20SCOP< 2,50
2,50SCOP< 2,80
2,80SCOP< 3,10
3,10SCOP< 3,40
3,40SCOP< 4,00
4,00SCOP< 4,60
4,60SCOP< 5,10
SCOP 5,10
5,60SEER < 6,10
6,10SEER < 8,50
SEER 8,50
5,10SEER < 5,60
4,60SEER < 5,10
4,10SEER < 4,60
3,60SEER < 4,10
3,10SEER < 3,60
2,60SEER < 3,10
SEER < 2,60
The Energy label is the regulation compliant way of displaying product efciency and sound level to any point of sales. 
This label displays 3 European climates: average climate (green), cold climate (blue), hot climate (orange). Regulation 
requirement is to display any information related to performances on average climate.
Climate used on ErP Temperature used for product selection
Average -10°C
Cold -22°C
Hot +2

Table of Contents

Other manuals for Hitachi UTOPIA R32 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi UTOPIA R32 Series and is the answer not in the manual?

Hitachi UTOPIA R32 Series Specifications

General IconGeneral
BrandHitachi
ModelUTOPIA R32 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals