EasyManuals Logo

Hitachi UTOPIA R32 Series Technical Catalogue

Hitachi UTOPIA R32 Series
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
9 Piping work and refrigerant charge
Copper pipes, sizes and connection
TCGB0136 rev.1 - 05/2021
91
9
? NOTE
• Donotusesaws,grindstoneorothertoolswhichmightcreatecopperdust.
• Whencuttingpipes,securetheparttobesolderedasshownintheServiceManual.
• Strictlyfollownationalorlocalregulationsregardingoccupationalhealthandsafety.
• Wearappropriatemeansofprotectionduringcuttingorbrazingoperationsandinstallation(gloves,eyeprotection,etc).
? NOTE
• Asystemwithnomoistureoroilcontaminationwillgivemaximumperformanceandlife-cycleascomparedwithapoorlyprepared
system.Takeparticularcaretoensurethatallcopperpipingiscleananddryinternally.
• Toensurethis,blowoxygenfreenitrogenthroughthepipes.
! CAUTION
• Captheendofthepipewhenthepipeistobeinsertedthroughahole.
• Donotplacepipesdirectlyonthegroundwithoutacaporvinyltapecoveringtheend,asitshowninthegure.
Right Wrong
• Ifpipinginstallationcannotbecompleteduntilthefollowingdayorlonger,soldertheendsofthepipingtoclosethemandloadwith
oxygen-freenitrogenusinganaccessdevicesuchasaSchradervalvetoavoidmoistureandcontaminationbyextraneousparticles.
• DonotuseinsulationmaterialcontainingNH3asitcandamagethecopperpipingmaterialandmaybeasourceoffutureleakage.
9.3.2 Insulation
Attach insulation to Multikit branch (eld-supplied or package with each one depending on model) using vinyl tape. Also 
attach insulation to eld-supplied piping to prevent capacity decrease due to  ambient air conditions and dewing on pipe 
surface caused by low pressure.
? NOTE
Whenpolyethylenefoamisapplied,athicknessof10mmfortheliquidpipingandfrom15mmto20mmforthegaspipingisrecommended.
! CAUTION
Performinsulationworkafterthesurfacetemperaturedecreasestotheroomtemperature,Ifnot,theinsulationmaterialmaymelt.Ifthe
endsofthepipingsystemareopenafternishingtheinstallationwork,securelyattachcapsorvinylbagstotheendsofthepipingto
preventmoistureordustentering.

Table of Contents

Other manuals for Hitachi UTOPIA R32 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi UTOPIA R32 Series and is the answer not in the manual?

Hitachi UTOPIA R32 Series Specifications

General IconGeneral
BrandHitachi
ModelUTOPIA R32 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals