Chapter  8  PROFINET  Specification 
The  current  output  frequency  isn’t  held.  Inverter 
runs by the output frequency. 
When  C006  is  HLD,  the  current  output  frequency  is 
held. 
The  output  frequency  is  set  Speed  Setpoint  A 
(NSOLL_A). 
The output frequency is set 0. 
Fault Acknowledge 
(0 -> 1) 
When  this  bit  is  changed  from  0  to  1,  errors  are 
cleared. 
When  the  state  is  “Operation”,  the  output 
frequency  is  0  and  bit4  -  6  are  0,  inverter  runs  by 
jogging. 
When inverter runs by jogging, Inverter stops. 
Inverter can be controled by PLC. 
Inverter can’t be controled by PLC. 
Inverter runs in reverse direction. 
Inverter runs in forward direction. 
Bit 11 is device specific. 
 
8.9 ZSW1 (Status word) 
The size of ZSW1 is 16 bits. 
The specification of each bit is the following. 
When  the  state  isn’t  “Switching  On  Inhibited”, 
this bit is ON. 
When the state is “Switching On Inhibited”, this bit 
is OFF. 
When the state is “Switched On”, “Operation” or 
“Switching Off (ramp stop or quick stop)”, this bit is 
ON. 
When  the  state  is  “Switching  On  Inhibited”  or 
“Ready For Switching On”, this bit is OFF. 
When the state is “Operation”, this bit is ON. 
When the state isn’t “Operation”, this bit is OFF. 
When error occurs in inverter or WJ-PN, this bit is ON. 
No error occurs in inverter or WJ-PN. 
Coast Stop Not Activated 
(No OFF 2) 
When STW1 bit1 is ON, this bit is ON.