Appendix PROFINET Object List
69
Index
Sub-
index
Register
number
Size
[bite]
Function
code
Name
R/W
Description and range
Resolution
WJ200
only
2000
0x4D
0x004B
04
(UDINT)
d086
Trip
information
6 (power-on
time)
R
Cumulative power-ON
time at trip point
1[h]
1000
0x4F
0x004E
02
(UINT)
d090
Warning
monitor
R
Warning code
-
1009
0x13
0x0900
02
(UINT)
-
Writing to
the
EEPROM
R/W
0: recalculation the
constant of the motor
1: stored the setting
value to the EEPROM
The others:
recalculation the
constant of the motor,
stored the setting
value to the EEPROM
-
-
1009
0x15
0x0902
02
(UINT)
-
Writing
mode
selection
R/W
0: writing enabled
1: writing disabled
-
1016
0x47
0x1026
02
(UINT)
d102
DC bus
voltage
monitor
R
0 to 10000
0.1[V]
1016
0x48
0x1027
02
(UINT)
d103
BRD load
ratio
monitor
R
0 to 1000
0.1[%]
1016
0x49
0x1028
02
(UINT)
d104
Electronic
thermal
monitor
R
0 to 1000
0.1[%]
Function mode: group F
Index
Sub-
index
Register
number
Size
[bite]
Function
code
Name
R/W
Description and
range
Resolution
WJ200
only
2000
0x02
0x0001
04
(UDINT)
F001
Output
frequency
setting
R/W
0 to the maximum
frequency (A004)
0.01[Hz]
2017
0x26
0x1103
04
(UDINT)
F002
Acceleration
(1) time
R/W
1 to 360000
0.01[s]
2017
0x28
0x1105
04
(UDINT)
F003
Deceleration
(1) time
R/W
1 to 360000
0.01[s]
1017
0x2A
0x1107
02
(UINT)
F004
Keypad Run
key routing
R/W
00: forward
01: reverse
-
2033
0x46
0x2103
04
(UDINT)
F202
Acceleration
(1) time,
2nd motor
R/W
1 to 360000
0.01[s]