EasyManua.ls Logo

Hitachi WL200 Series

Hitachi WL200 Series
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix PROFINET Object List
70
Index
Sub-
index
Register
number
Size
[bite]
Function
code
Name
R/W
Description and
range
Resolution
WJ200
only
2033
0x48
0x2105
04
(UDINT)
F203
Deceleration
(1) time,
2nd motor
R/W
1 to 360000
0.01[s]
Function mode: group A
Index
Sub-
inde
x
Register
number
Size
[bite]
Functio
n
code
Name
R/W
Description and range
Resolutio
n
WJ200
only
1018
0x26
0x1201
02
(UINT)
A001
Frequency
source
R/W
00: volume
01: control terminal
02: function F001
setting
03: Modbus network
input
04: option board
06: pulse train input
07: EzSQ
10: calculate function
output
-
1018
0x27
0x1202
02
(UINT)
A002
Run
command
source
R/W
00: control terminal
01: run key on the
keypad, or digital
operator
02: Modbus network
input
03: option
-
1018
0x28
0x1203
02
(UINT)
A003
Base
frequency
R/W
300 to the maximum
frequency (A004)
0.1[Hz]
1018
0x29
0x1204
02
(UINT)
A004
Maximum
frequency
R/W
300 to 4000
0.1[Hz]
1018
0x2A
0x1205
02
(UINT)
A005
[AT]
selection
R/W
00: select between [O]
and [OI] at [AT] (ON =
OI, OFF = O)
02: select between [O]
and external POT at
[AT] (ON =POT, OFF =
O)
03: select between
[OI] and external POT
at [AT] (ON =POT, OFF
= OI)
-
2018
0x30
0x120B
04
(UDINT)
A011
[O] input
active range
start
frequency
R/W
0 to 40000
0.01[Hz]