YUTAKI S COMBI
Model Power supply Operation mode Z
max
(Ω)
RWD-(2.0-3.0)
NW(S)E-(200/260)S
1~ 230V 50Hz
Without electric heaters -
With electric heater -
With DHW tank heater -
With electric and DHW tank heaters 0.28
RWD-(4.0-6.0)
NW(S)E-(200/260)S
1~ 230V 50Hz
Without electric heaters -
With electric heater 0.26
With DHW tank heater -
With electric and DHW tank heaters 0.18
3N~ 400V 50Hz
Without electric heaters -
With electric heater
-
With DHW tank heater -
With electric and DHW tank heaters
-
YUTAKI S80
Indoor unit alone
Model Power supply Operation mode Z
max
(Ω)
RWH-4.0VNFE
1~ 230V 50Hz
Without DHW tank heater 0.31
With DHW tank heater 0.20
RWH-5.0VNFE
Without DHW tank heater 0.27
With DHW tank heater 0.18
RWH-6.0VNFE
Without DHW tank heater 0.24
With DHW tank heater 0.17
RWH-4.0NFE
3N~ 400V 50Hz
Without DHW tank heater -
With DHW tank heater 0.38
RWH-5.0NFE
Without DHW tank heater -
With DHW tank heater 0.38
RWH-6.0NFE
Without DHW tank heater -
With DHW tank heater 0.38
Indoor unit in combination with DHW tank
Model Power supply Operation mode Z
max
(Ω)
RWH-4.0VNFWE
1~ 230V 50Hz
Without DHW tank heater 0.31
With DHW tank heater 0.21
RWH-5.0VNFWE
Without DHW tank heater 0.27
With DHW tank heater 0.19
RWH-6.0VNFWE
Without DHW tank heater 0.24
With DHW tank heater 0.17
RWH-4.0NFWE
3N~ 400V 50Hz
Without DHW tank heater -
With DHW tank heater 0.41
RWH-5.0NFWE
Without DHW tank heater -
With DHW tank heater 0.41
RWH-6.0NFWE
Without DHW tank heater -
With DHW tank heater 0.41
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the YUTAKI S80 domestic hot water tank accessory
“DHWS(200/260) S-2.7H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0335A rev.1 - 04/2016
92