4 WORKING RANGE
4.1 POWER SUPPLY WORKING RANGE
Nominal power supply
Single phase: 1~ 230V 50Hz
Three phase: 3N~ 400V 50Hz
Operating voltage
Between 90 and 110% of the nominal voltage.
Voltage imbalance for nominal power supply 3N~ 400V 50Hz
Up to 3% of each phase, measured at the main terminal of the outdoor unit.
Starting voltage
Always higher than 85% of the nominal voltage.
4.2 TEMPERATURE WORKING RANGE
MODEL 2.0HP 2.5HP 3.0HP 4.0HP 5.0HP 6.0HP 8.0HP 10.0HP
Water temperature
ºC
Refer to the graphics for each case
Indoor ambient temperature 5~30
4.2.1 Space heating
YUTAKI (S / S COMBI)
(2.0-3.0)HP (4.0-10.0)HP
Water outlet
temperature (Cº)
Ambient
temperature (ºC(DB))
Water outlet
temperature (Cº)
Ambient
temperature (ºC(DB))
Continuous working range.
Outdoor unit operation is possible, but the capacity is not guaranteed. Indoor unit and back-up heater are operating.
Only back-up heater. (No outdoor unit operation).
WORKING RANGE
PMML0335A rev.1 - 04/2016
65

Table of Contents

Other manuals for Hitachi YUTAKI RWM-2R1E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi YUTAKI RWM-2R1E and is the answer not in the manual?

Hitachi YUTAKI RWM-2R1E Specifications

General IconGeneral
BrandHitachi
ModelYUTAKI RWM-2R1E
CategoryAir Conditioner
LanguageEnglish

Related product manuals