contact that is caused by the loosened terminal connections, the oxidized contacts, the foreign matter and other items. Check the
electrical insulation resistance.
6 Control device and protection device
Setting: Do not readjust the setting in the eld unless the setting is maintained at a point that is different from the point listed in
the Technical Documentation.
7 R410A compressor
Sound and vibration: Check for abnormal sounds and vibrations.
Activation: Check that the voltage drop of the power supply line is within 15% at the start and within 2% during the operation.
8 Reverse valve
Activation: Check for any abnormal activation sound.
9 Strainer
Clog: Check that there is no temperature difference between both ends.
10 Ground wire
Ground line: Check for the continuity to earth.
11 Oil heater (Crankcase heater of the R-410A compressor)
Activation: The oil heater should be activated at least twelve hours before the start-up by turning ON the main switch.
10.1.2 General maintenance procedure for the indoor unit
To ensure good operation and reliability of the indoor unit, main parts and eld wiring have to be checked periodically.
The following checks have to be done by qualied technicians at least once a year:
1 Cabinet
Stain: Check for any stain and remove it cleaning if it is the case.
Fixing screw: Check for any loosened screw or any lost screw. Tighten the loosened screws and replace the lost screws.
Insulation material: Check for any peeled thermal insulator on the indoor part of the covers. Repair the thermal insulator.
2 Water piping connection
Leakage: Check there are no water leakages neither in the inlet and outlet water connections (space heating and DHW if
used), nor in the main water circuit nor the tank connections. Check all the joints, connections and circuit elements.
? NOTE
If leakage is detected in the inlet/outlet water connections, repair it and remember to replace the gaskets.
Pay special attention to the water pipe connection placed over the electrical box.
3 Water ow and pressure:
Water ow:
- Space heating: Check the water ow (m
3
/h) through the unit controller in the “Heat Pump Details” of the “Operation
Information” menu.
- DHW (if used): Check whether the water circulation is correct along all the DHW circuit.
Pressure checking:
- Space heating: Check the water pressure using the manometer in the indoor unit (In YUTAKI M units, this manometer is
eld supplied). This value shall be between 1.5 and 2.0 bars approximately (1.8 bars is a proper value).
MAINTENANCE
PMML0335A rev.1 - 04/2016
175

Table of Contents

Other manuals for Hitachi YUTAKI RWM-2R1E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi YUTAKI RWM-2R1E and is the answer not in the manual?

Hitachi YUTAKI RWM-2R1E Specifications

General IconGeneral
BrandHitachi
ModelYUTAKI RWM-2R1E
CategoryAir Conditioner
LanguageEnglish

Related product manuals