ENGLISH
Split system - Indoor unit
YUTAKI S
Model Power supply
Applicable voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max.
(V)
U min.
(V)
RWM-(2.0-3.0)NE 1~ 230V 50Hz 253 207
Without electric heaters
0.2 5
2/40/30
With electric heater
15 16
With DHW tank heater
15 16
With electric and DHW tank heaters
29 32
RWM-(4.0-6.0)NE
1~ 230V 50Hz 253 207
Without electric heaters
0.3 5
2/40/30
With electric heater
29 32
With DHW tank heater
15 16
With electric and DHW tank heaters
43 50 2/63/30
3N~ 400V 50Hz 440 360
Without electric heaters
0.3
5
4/40/30
With electric heater
10 15
With DHW tank heater
15 15
With electric and DHW tank heaters
24 25
RWM-(8.0/10.0)NE 3N~ 400V 50Hz 440 360
Without electric heaters
0.6
5
4/40/30
With electric heater
15
20
With DHW tank heater
15 15
With electric and DHW tank heaters
29 30
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
YUTAKI S COMBI
Model Power supply
Applicable voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max.
(V)
U min.
(V)
RWD-(2.0-3.0)
NW(S)E-(200/260)S(-K)
1~ 230V 50Hz 253 207
Without electric heaters
0.2 5
2/40/30
With electric heater
15 16
With DHW tank heater
13 16
With electric and DHW tank heaters
27 32
RWD-(4.0-6.0)
NW(S)E-(200/260)S(-K)
1~ 230V 50Hz 253 207
Without electric heaters
0.3 5
2/40/30
With electric heater
29 32
With DHW tank heater
13 16
With electric and DHW tank heaters
42 50 2/63/30
3N~ 400V 50Hz 440 360
Without electric heaters
0.3 5
4/40/30
With electric heater
10 15
With DHW tank heater
13 15
With electric and DHW tank heaters
22 25
ELECTRICAL AND CONTROL SETTINGS
PMML0335A rev.1 - 04/2016
97