Model RWM-8.0NE RWM-10.0NE
Power supply - 3N~ 400V 50Hz
Noise level (sound power) dB(A) 47 47
Cabinet
Material - Precoated galvanised steel
Colour - Pure white (RAL 9010)
Unit dimensions
Height (with connections) mm 890 (960)
Width mm 670
Depth mm 360
Packaging
dimensions
Height mm 546
Width mm 1120
Depth mm 760
Packaging volume 0.46
Packaging materials - Wood - Carton - Plastic
Net weight kg 76 80
Gross weight kg 90 93
Refrigerant pipes
connection
Connection type - Liquid pipe: Flare nut connection; Gas pipe: Brazed connection
Liquid pipe diameter mm (in.) Ø9.52 (3/8”) Ø12.7 (3/8”)
Gas pipe diameter mm (in.) Ø25.4 (1”)
Space heating pipes
connection
Connection type - Screwed connection
Shut-off valves mm (in.) G 1-1/4” (male) - G 1-1/4” (male)
Inlet pipe diameter mm (in.) G 1-1/4” (female)
Outlet pipe diameter mm (in.) G 1-1/4” (female)
Working range
(Heating)
Outdoor ambient temperature ºC (DB) -25~25
Outlet water temperature ºC 20~60
Working range
(Cooling)
Outdoor ambient temperature ºC (DB) 10~46
Outlet water temperature ºC 5~22
Working range (DHW)
Outdoor ambient temperature ºC (DB) -25~35
Tank water temperature ºC 30~75
GENERAL DATA
PMML0335A rev.1 - 04/2016
38

Table of Contents

Other manuals for Hitachi YUTAKI RWM-2R1E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi YUTAKI RWM-2R1E and is the answer not in the manual?

Hitachi YUTAKI RWM-2R1E Specifications

General IconGeneral
BrandHitachi
ModelYUTAKI RWM-2R1E
CategoryAir Conditioner
LanguageEnglish

Related product manuals