Questions Description Default Value Range Steps Units Application
Notes
Controller Conguration S SC S80 M
Question 11
How many
thermostats are
installed?
0
0
1 -
If question 3 has been
answered with a different
answer than “No”,
Conguration Assistant task
will have nished after this
question, since the room
thermostats have to be
connected as “Wired” (Mixed
conguration (Wireless +
Wired) is not allowed).
The number of possible
installed thermostats depends
on the answers of question 3.
1
2
Question 12
How are they
connected?
Wired
Wired
- -
Only available when question
11 has been answered with
“1” or “2” and if one of the
following conditions:
- question 1 answered as “Yes”
and question 3 as “No”
- question 1 answered as “No”
and question 3 as “No
Wireless
IMPORTANT:
Always start the conguration from the Master. In case of using “advanced conguration”, Room PC-ARFH should be congured
before start the “check RT address” procedure.
After the question 3, information is send between the PC-ARFH, so for example:
- If rst PC-ARFH has been congured as Master, the other PC-ARFH cannot be Master and it is blocked to answer only the
Question 3.
After the question 4, information is send between the PC-ARFH, so for example:
- If rst PC-ARFH has only 1 circuit, the other PC-ARFH cannot control zone 2.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
121