Hitachi YUTAKI S80 Series - Space Cooling; Eco Offset; Working Limits

Hitachi YUTAKI S80 Series
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH
CODE
SandSC S80 M
Units
2-3HP REST ALL 3HP REST
A 44 44 70 (**) 44 ºC
B 20 20 20 20 ºC
C 0.6 0.6 1.4 0.6 -
D 40 40 70 (**) 40 ºC
E 55 60 80 (**) 60 ºC
F 55(*) 60(*) 80 (**) 55 (*) 60 (*) ºC
- (*) In case of Boiler combination complementary heating activation (Heating source (HES) = Boiler or Boiler + Heater) maximum supply
temperature range can be setting up to 80ºC:
- (**): If R134a compressor disabled (DSW4#1: ON) setting must be 60ºC.
(*2) OFF means “Disabled”.
8.6.2.5 Space Cooling
If Controller type (LCDM)= “Unit” or “Unit + Room”.
Circuit 1 and Circuit 2
REF Access Description
Default
Value
Range Steps Units Application
Notes
Working Limits S SC S80 M
CC1WC Water Calculation Mode (Circuit 1) Gradient
Disabled
Point
Fix
1 - - -
CC1ECO ECO offset water set.(Circuit 1) 3 1~10 1 ºC - (*1)
CC2WC Water Calculation Mode (Circuit 2) Disabled
Disabled
Point
Fix
1 - - -
CC2ECO ECO offset water set. (Circuit 2) 3 1~10 1 ºC - -
- Working Limits (Circuit 1 and 2) - - - - - (*3)
-
Mixing Valve (Circuit 2) - - - - - (*2)
? NOTE
(*1): If Water calculation mode for circuit 1 cooling (CC1WC) is not set as “Disabled”.
(*2): If Water calculation mode for circuit 2 cooling (CC2WC) is not set as “Disabled”.
(*3): If Water calculation mode for circuit 1 cooling (CC1WC) or Water calculation mode for circuit 2 cooling (CC2WC) are not set as “Disabled”.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
147