ENGLISH
DHW Anti Legionella
Status
Operation Day
Starting Time
Setting Temperature
Duration
REF Access Description
Default
Value
Range Steps Units Application
Notes
Anti Legionella S SC S80 M
DesFun Status Disabled
Disabled /
Enabled
- - -
OpInt Operation Day Sunday Daily / Mon ~ Sun - day (*1)
StTim Starting Time 01:00 (00:00~ 23:50) 00:10 time (*1)
SHWTS Setting Temperature 70 (*2) 50~A - ºC (*1)(*)
KeepP Duration 10 10~60 - min (*1)
? NOTE
(*1):If Status (DesFun)= “Enabled”.
(*2): 70 or “A” if “A”<70.
(*) Refer to the table:
Model
YUTAKI S & COMBI YUTAKI S80 YUTAKI M
(2.0-3.0)HP REST (4.0-6.0)HP 3HP REST
A 50ºC (1) 55ºC (1) 75ºC (2) 50ºC (1) 55ºC (2)
- (1): 75 ºC when DHW tank’s heater is enabled (DSW4-3: ON) or Combination mode (BOCM)= “Parallel” and DHW by boiler (BODHW)
“Enabled” in “Boiler combination” option of the “Complementary heating” menu.
- (2): If the conditions of (1) are no satised and the R-134a compressor is disabled (DSW4-1: ON) of the “Complementary heating” menu, the
setting must be 55 ºC.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
151