Solar Combination
REF Access Description
Default
Value
Range Steps Units Application
Notes
Solar combination S SC S80 M
SOLStSet Status Disabled
Disabled
Input demand
Total control
- - (*1)
? NOTE
(*1): Forced to disabled if Status (DHWs)= “Disabled”.
Input demand
REF Access Description
Default
Value
Range Steps Units Application
Notes
Input demand S SC S80 M
SOLHy
DHW Hysteresis 10 1-30 5 min (*1)
SOLmxt
DHW Maximum Time 60 30~240 5 min (*1)
? NOTE
(*1): Available if Solar combination (SOLStSet) = “Input Demand” and Status (DHWs) = “Enabled”.
Total control
REF Access Description
Default
Value
Range Steps Units Application
Notes
Total control S SC S80 M
SOLmxt DHW Maximum Time 60 30~240 5 min -
TDHWTMAX
DHWT Max storage T 60 30-90 1 ºC -
SOLSdTc
∆T Connexion 10 1~30 1 ºC -
SOLSdTc ∆T Disconnection 5 1~30 1 ºC -
Solarmin Panel Minimum T 15 1~60 1 ºC -
SOLOver Panel Overheat T 80 80~120 1 ºC -
SOLAnz
Panel antifreeze T 4 -20~10 1 ºC (*1)
? NOTE
(*1): 0 means OFF.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
154