7.8.2.4  Space Heating / Space Cooling conguration
Control the temperature for Space Heating or Space Cooling by conguring the following parameters.
Working Limits: 
Limit  for  the  temperature  set-point  to 
prevent  high  or  low  temperatures  at 
Space Heating or Space Cooling:
•  Maximum supply temperature 
•  Minimum supply temperature
Water calculation mode: 
Selection of the water set point for 
Circuit 1 or Circuit 2 (Space Heating 
or Space Cooling).
•  Disabled
•  Points
•  Gradient (only in heating mode)
•  Fix
See detailed explanation below.
Eco Offset Water setting: 
Congure the offset water temperature 
for the ECO mode for Space Heating 
or Space Cooling. 
By using this function, current water 
temperature setting is reduced by the 
indicated parameter.
•  Range: -10 ~ 10
Mixing valve: 
To  control  the  second  water  temperature  (only  for 
circuit 2).
Values  are  adjusted  for  the  use  with  the  2nd  zone 
mixing  kit  accessory  ATW-2KT-05.  It  is  highly 
recommended not to change these values.
In case of using a mixing kit different from the ATW-
2KT-05 congure the following parameters:
•  Proportional band: 0 ~20 K (6.0 K by default). 
•  Integral reset factor: 0.0 ~20 % (2.5 % by default).
•  Running  time  factor:  10  ~250  sec  (140  sec  by 
default).
•  Over temperature offset protection: OFF, 3 ~10 ºC 
(5 ºC by default).
UNIT CONTROLLER
PMML0510 rev.1 - 10/2019
96