EasyManua.ls Logo

Hitachi YUTAKI Series - Heat Pump Configuration

Hitachi YUTAKI Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH
7.8.2.8 Heat Pump conguration
Water pump conguration:
Congure the water pump of the
heat pump.
See detailed information in the
next page.
Night shift:
Reduces compressor load in order
to reduce environmental noise,
preferably at night.
See detailed information in the next
page.
Minimum ON time: In order to reduce a possible
compressor damage, demand ON cycles can be
reduced by determining the time that must pass
before accepting new Demand OFF.
Minimum OFF time: In order to reduce a
possible compressor damage, demand OFF
cycles can be reduced by determining the time
that must pass before accepting new Demand
ON.
Seizure protection: The pump seizure protection
function prevents sticking of components due
to long periods of inactivity, by running the
components during a short period every week.
Mixing valves and pumps are fully opened and
then fully closed (time depends on Mixing valve
Run Time Factor).
Outdoor average temperature:
OTC average is used to neutralise the effect of
occasional temperature variations.
The average value of outdoor temperature sampled
over a selected period (between 1 and 24 hours) is
used for the calculation of weather-dependent set point
temperature.
1 / 2
2 / 2
UNIT CONTROLLER
PMML0510 rev.1 - 10/2019
103

Table of Contents

Other manuals for Hitachi YUTAKI Series

Related product manuals