4.3.4  Space cooling (Necessary cooling kit)
Water outlet 
temperature (ºC)
Ambient temperature 
(ºC(DB))
Refreshing oor 
working area
Fan coil working 
area
 Continuous working range.
 Maximum setting temperature. 
 Minimum setting temperature. 
4.4  R410A HYDRAULIC WORKING RANGE
4.4.1  Hydraulic data
 
YUTAKI S
MODEL 2.0 HP 2.5 HP 3.0 HP 4.0 HP 5.0 HP 6.0 HP 8.0 HP 10.0 HP
Minimum water ow rate (*1) m
3
/h 0.5 0.6 0.6 1.0 1.1 1.2 2.0 2.2
Maximum water ow rate (*1) m
3
/h 1.9 2.0 2.1 2.9 3.0 3.0 4.5 4.6
Minimum installation water volume (*2)  l 28 28 28 38 46 55 76 79
Minimum allowable water pressure MPa 0.1
Maximum allowable water pressure MPa 0.3
 
YUTAKI S COMBI
MODEL 2.0 HP 2.5 HP 3.0 HP 4.0 HP 5.0 HP 6.0 HP
Minimum water ow rate (*1) m
3
/h 0.5 0.6 0.6 1.0 1.1 1.2
Maximum water ow rate (*1) m
3
/h 1.8 1.9 1.9 2.7 2.8 2.8
Minimum installation water volume (*2)  l 28 28 28 38 46 55
Minimum allowable water pressure MPa 0.1
Maximum allowable water pressure MPa 0.3
 
YUTAKI S80
MODEL
4.0 HP 5.0 HP 6.0 HP
Version for 
indoor unit 
alone
Version for 
combination 
with DHW 
tank
Version for 
indoor unit 
alone
Version for 
combination 
with DHW 
tank
Version for 
indoor unit 
alone
Version for 
combination 
with DHW 
tank
Minimum water ow rate (*1) m
3
/h 1.0 1.1 1.2
Maximum water ow rate (*1) m
3
/h 2.8 2.5 3.2 2.7 3.2 2.7
Minimum installation water volume (*2)  l 40 50 50
Minimum allowable water pressure MPa 0.1
Maximum allowable water pressure MPa 0.3
WORKING RANGE
PMML0510 rev.1 - 10/2019
26