CASCADE conguration
Modules conguration:
Congure the status, refrigerant cycle
address, indoor unit address and individual
DHW for each module.
Module status:
Enable or disable the module.
Individual DHW status:
Enable or disable the individual DHW
for the selected module.
Individual DHW type:
Select Master or Slave depending on the
installation of the DHW system.
When Slave type is selected, choose the
master module number.
Refrigerant cycle address:
Set the refrigerant cycle address for each
module, making sure that the setting is
common with that of the outdoor (DSW4-
RSW1) and indoor (DSW15 – RSW2) units
which are part of the module.
Indoor unit address:
It must be always set to 0 (factory default)
Individual DHW:
Congure the status and type of individual
DHW for the selected module.
Supply setting offset
To set YUTAKI Slave Units to
work at a setting temperature
higher than setting temperature
determined by YUTAKI
CASCADE CONTROLLER
3 ºC by default (from 0 to 15 ºC)
YUTAKI CASCADE CONTROLLER
PMML0510 rev.1 - 10/2019