EasyManua.ls Logo

Hitachi YUTAKI Series - Page 66

Hitachi YUTAKI Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monobloc system - R32 YUTAKI M
Model
Power
supply
Applicable
voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max.
(V)
U min.
(V)
RASM-2VRE
1~ 230V
50Hz
253 207
Without DHW tank heater 10.6 16
2/40/30
With DHW tank heater 23.1 32
RASM-3VRE
Without DHW tank heater 16.0 20
With DHW tank heater 28.5 32
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0510 rev.1 - 10/2019
56

Table of Contents

Other manuals for Hitachi YUTAKI Series

Related product manuals