18 AS302P Single Phase Smart Meter
____________________________________________________________________
© Honeywell - M450 001 1D - 23.05.2019
For each TOU, the Energy usage (in kWh’s) is accumulated until Block Threshold 1 is reached. The sequence is then
repeated up to Block Threshold 2, with any Energy usage above the Block 2 Threshold accumulated in Block 3.
The Maximum Block Configuration is 8 TOU, 4 Blocks, allowing up to 32 Price Bands in total.
The TOU Rate Definitions are defined in the same way as the TOU Tariff.
Special Days can be programmed to override the Block Tariff.
The Tariff Block Register Counters (rising) will be reset in line with the Billing Calendar, these can also be reset on receipt
of a command.
11.3.1. TOU Block Price Matrix
The TOU Block Price Matrix is for Import Active Energy only and contains 8 x 4 prices.
The TOU Block Price Matrix can be programmed to be activated at a specified Activation Date/Time.
The TOU Block Price Matrix for the TOU Block Tariff is shown below:
11.3.2. Maximum Demands
The AS302P calculates and stores the following Maximum Demands:
Maximum Demand Active Power Import Value
Maximum Demand (Configurable Time Active Power Import Value)
Maximum Demand Active Power Export Value
These values can be reset on a receipt of an appropriate command (any value or all values can be reset with this
command).