Configuring CDA
CDAis short for Control Data Access. CDA protocol supports peer to
peer communication between ControlEdge 900 controller with C300
controller or ACE or SIM-300 or SIM-ACE. ControlEdge 900
controller acts as the CDA responder and C300 Controller(or the
others mentioned above) acts as the CDAinitiator.
It supports:
n Maximum 20 CDA initiators connected to a single CPM
n Maximum 1000 PPS (parameters per second) between CDA
initiators and CPM
n Both read and write access from C300 or ACE Controller
n Read access from SIM-300 or SIM-ACE
n Communication Security including IPsec and embedded Firewall
To configure a CDAresponder, perform the following steps:
In this section:
Installing ControlEdge integration service 107
Configuring a CDA Responder 108
Publishing to Experion 110
106
Chapter 6 - Communication