22 E
3
Point Network Gas Monitor User Manual
Using the Programming Menus
• Press enter to confirm, or use the arrow keys to scroll to No to
cancel. The screen displays the concentration during calibration.
Set Span
198 ppm
A success or failure message displays and the screen returns to the
main menu option.
TestMode Menu
The TestMode menu performs a test of all functions on the unit. All
outputs are activated according to their failsafe mode, relay setting, and
buzzer setting. All functions are activated simultaneously for a maximum
of 3 minutes, or until the user cancels the test. The unit does not
detect gas during this TestMode procedure. Press enter to access the
TestMode.
* Menu *
TestMode
• Use the arrow keys to scroll to Yes or No and press any key to
begin the test sequence
TestMode
Yes
• To cancel the test, press enter at anytime when Stop displays.
TestMode
Stop