Enhanced Micro TDC 3000
User’s Manual A-6 9/95
A
Parameter
APM_SEQ
Parameter
APM_SEQ
NAME "APM_SEQ" USERID “----------------”
PNTFORM FULL STRLEN 8
PNTDESC “APM SEQUENCE PROGRAM” SEQSLTSZ 20
UNIT 01 CNTLLOCK OPERATOR
NTWKNUM 01 SPLOCK OPERATOR
NODENUM 3 RSTROPT RESTART
SLOTNUM 1 ACP --
PRIMOD -- SEQPR NOACTION
Parameter
APM_DIF
Parameter
APM_DIF
NAME "APM_DIF" STATETXT(1) “OPEN“
PNTFORM FULL STATETXT(0) “CLOSED“
PNTDESC “APM FULL DIGITAL INPUT” BOXCLR(1) GREEN
EUDESC "BLOCK“ BOXCLR(0) BLUE
KEYWORD "VALVE" INPTDIR DIRECT
UNIT 01 PVSRCOPT ALL
NTWKNUM 01 PVSOURCE AUTO
NODENUM 3 ALMOPT OFFNORML
MODNUM 3 PVNORMAL CLOSED
SLOTNUM 1 DLYTIME 10
PRIMMOD -- OFFNRMPR NOACTION
PNTMODTY DI ALENBST ENABLE
DITYPE STATUS EVTOPT NONE
Parameter
APM_D0C
Parameter
APM_D0C
NAME "APM_D0C" NTWKNUM 01
PNTFORM COMPONNT NODENUM 3
PTDESC “ “ MODNUM 4
EUDESC “????????” SLOTNUM 1
KEYWORD “????????” PNTMODTY DO
UNIT 01 DOTYPE STATUS